Appendix B Fieldbus Parameters
© National Instruments Corporation B-7 FieldPoint FP-3000 User Manual
DISC_PRI (Alarming)
Priority of the discrete alarm.
DV_HI_ALM (Alarming)
The current state of the deviation high alarm, along with a time and date
stamp.
DV_HI_LIM (Alarming)
The deviation limit between the PID block setpoint and process value, in
engineering units, beyond which the deviation high alarm is considered
active.
DV_HI_PRI (Alarming)
The priority of the deviation high alarm.
DV_LO_ALM (Alarming)
The current state of the deviation low alarm, along with a time and date
stamp.
DV_LO_LIM (Alarming)
The deviation limit between the PID block setpoint and process value, in
engineering units, beyond which the deviation low alarm is considered
active.
DV_LO_PRI (Alarming)
The priority of the deviation low alarm.
FAULT_STATE (Faultstate, Option)
The current status of the device faultstate. It can be set and cleared with
SET_FSTATE
and
CLR_FSTATE
. If it is set, all output blocks in the device
initiate their own faultstate behavior.
FEATURE_SEL/FEATURES (Diagnostic, Option)
The
FEATURES
parameter lists features supported by the device. Use the
FEATURE_SEL
parameter to manually enable and disable the supported
features listed in the
FEATURES
parameter.