Chapter 2 Installation and Configuration
© National Instruments Corporation 2-9 FieldPoint FP-3000 User Manual
Hot-swap a module only with a compatible module. If you hot-swap a
module with an incompatible module, the associated function blocks must
be entirely reconfigured.
Connect the FP-3000 to the Fieldbus Network
The FP-3000 can be one of up to 32 devices connected to a Fieldbus
network. The connection is made through the 9-pin male Dsub Fieldbus
connector on the FP-3000, shown in Figure 2-6.
Figure 2-6. Fieldbus Connectors on the FP-3000
Use a Fieldbus cable with a 9-pin female Dsub connector to connect the
FP-3000 to a properly terminated Fieldbus network. When you are only
using an FP-3000, the power hub is not being used for powerit is only
being used because it has the terminators inside. For other F
OUNDATION
Fieldbus devices that use bus powering, you would apply power to the hub,
from which devices would get their power. Refer to the Fieldbus
Foundation Wiring and Installation 31.25 kbit/s, Voltage Mode, Wire
Medium Application Guide for specific information about wiring and
installing a Fieldbus network. If you want to make your own Fieldbus cable,
refer to the Fieldbus Standard for Use in Industrial Control Systems,
Part 2, ISA-S50.02.1992. The FP-3000 Fieldbus connector pinout is shown
in Figure 2-7.
Power
Connector
Dsub
Fieldbus
Connector
Local Bus Connector
Status
LEDs