Appendix C FP-3000 Specific Parameters
FieldPoint FP-3000 User Manual C-2 www.ni.com
BLOCK_ALMS_ACT
A more detailed explanation of the active block alarms.
BLOCK_RESET
Lets you reset the statistics or the configuration of an individual function
block.
CFG_OPTS
An option in the I/O function blocks to automatically set the scaling or alter
the block behavior. Generally, this option can make configuration easier.
CHECKBACK
A list describing the state of the interlock logic in the CDO block. Use
CHECKBACK
to determine how interlocks are operating.
Table C-1. Block Reset Options
Option Description
Contained Parameters Sets all the contained parameters (standard and FP-3000
specific) of the function block to default values. This is useful to
set a specific block to a known state without affecting the
behavior of the other blocks in the FP-3000. The block should
be in
OOS
mode to reset the contained parameters.
Statistics Resets the various statistics counts associated with the block.
Table C-2. Configuration Options
Option Description
Automatically Adjust
XD_SCALE
Enabling this option allows the block to automatically
determine its
XD_SCALE
parameter, based on the physical
I/O channel range, which is set by parameters such as
FP_AI_100
range.
Ignore Unconnected Interlock
Inputs
By default, all interlock inputs on the CDO block must be
good, or the block enters fault state. Enabling this option allows
inputs with a status of
Bad::Not_Connected
to be ignored.