
Appendix C FP-3000 Specific Parameters
FieldPoint FP-3000 User Manual C-10 www.ni.com
OP_CMD_CXO
The lowest level priority input. This can be used to allow the operator to
activate interlock behavior with a write from the host application.
RUN_STATUS
The current run status of the block (used for debugging).
RUN_TIME
The time the block took to run (including overhead).
SAFEGUARD_CL
An interlock input. When in
Discret_State_1
, the output of the block is
forced closed (
Discret_State_0
). This interlock input has priority over
all other interlock inputs.
SAFEGUARD_OP
An interlock input. When in
Discret_State_1
, the output of the block is
forced open (
Discret_State_1
). This interlock input has priority over all
other interlock inputs except
SAFEGUARD_CL
.
SUPPORTED_MODES
The modes supported by the block.
Table C-8. Command Parameters
Val ue Description
Close When this flag is set, the output of the block is forced to
Discret_State_0
. This interlock is overridden by every other
interlock. If both
OP_CMD_CXO.Close
and
OP_CMD_CXO.Open
are set,
theyarebothconsideredtobeclear.
Open When this flag is set, the output of the block is forced to
Discret_State_1
. This interlock is overridden by every other
interlock. If both
OP_CMD_CXO.Close
and
OP_CMD_CXO.Open
are set,
theyarebothconsideredtobeclear.
Stop Unused in FieldPoint.
Enable 1, 2, 3 Unused in FieldPoint.
Kommentare zu diesen Handbüchern