Chapter 4 Block Reference
©
National Instruments Corporation 4-15 FieldPoint FP-3000 User Manual
FP_AO_200_RANGE
Allows the range of a channel on a FieldPoint FP-AO-200 to be adjusted.
FP_CJC_SOURCE
Allows the cold junction compensation to be adjusted on a FP-TC-120
module.
Note
Cold junction compensation is global to the entire module and affects every channel
on the module.
FP_MOD_STATUS
The status of the FieldPoint I/O module associated with the function block.
FP_NOISE_REJECTION
Allows the noise rejection filter of an Analog Input module to be adjusted.
Table 4-10.
Module Status
Status Description
No Base There is no terminal base in the specified
module position.
Base, But No Module There is a terminal base in the specified
module position, but no module is installed
in the base.
Unconfigured Module There is a module in the specified position,
but the FP-3000 is unable to configure it.
Module in
Configuration
There is a module in the specified position,
the FP-3000 has attempted to configure the
module, and the module is in the process of
configuration.
Module Okay There is a module in the specified position,
and it is configured and operating correctly.
Incorrect Module
for Block
There is a module in the specified position,
but the block is incompatible with the
module.